  • Full range of PAT testing functions including insulation and RCD tests
  • Onboard memory for up to 1000 results with QWERTY keyboard for data entry
  • Intuitive operation with individual test buttons and an auto mode

Optional Extras

£1,129.00+VAT
In stock
+

Description

The Fluke 6500-2 PAT Tester is a sleek, sophisticated instrument that can perform tests on Class I appliances, Class II appliances and IEC/extension leads. It can execute a multitude of tests including earth bond testing, insulation resistance testing, and polarity checking. These basic features are supplemented by a high current 25A earth bond test and a 250V insulation test which is compatible with surge protection. Other tests include leakage current, load & run testing, and RCD testing.

Specific individual buttons on the Fluke 6500-2 trigger individual tests which means the tester is suitable for manual testing. An automatic test mode is also available for more rapid testing. There is a full QWERTY keyboard that can be used to enter appliance information to the onboard memory and the tester has enough space for 1000 test results.

Numerical test results and a PASS/FAIL indication are provided on the Fluke 6500-2’s vibrant colour display. It is possible to navigate through the menu-based operation and saved data on the tester using the direction buttons and files can be saved to a USB drive in order to be transferred to a PC. It is also possible to print hard copies and PAT labels using an optional Fluke SP6000 printer.

Key Features

  • High current 25A earth bond test
  • 250V insulation resistance test
  • Leakage current measurement
  • Load and run test (230V)
  • Portable RCD testing
  • Manual and automatic testing
  • Simple operation
  • Full QWERTY keyboard
  • Onboard memory for 1000 results
  • Vibrant LCD display

Specification

Power-on Test

  • The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
  • Display Range : 90 V to 264 V
  • Accuracy at 50 Hz: ± (2% + 3 counts)
  • Resolution: 0.1 V
  • Input Impedance: > 1 MΩ // 2.2 nF
  • Maximum Input Mains Voltage: 264 V

Earth Bond Test (Rpe)

  • Display Range: 0 to 19.99 Ω
  • Accuracy (After Bond Test Zeroing): ± (5% + 4 counts)
  • Resolution: 0.01 Ω
  • Test Current: 200 mA AC -0% +40% into 1.99 Ω; 25 A AC ± 20% into 25 mΩ at 230 V
  • Open Circuit Voltage: > 4 V AC, < 24 V AC
  • Bond Test Zeroing: Can subtract up to 1.99 Ω

Insulation Test (Riso)

  • Display Range: 0 to 299 MΩ
  • Accuracy: ± (5% + 2 counts) from 0.1 to 300 MΩ
  • Resolution: 0.01 MΩ (0 to 19.99 MΩ) / 0.1 MΩ (20 to 199.9 MΩ) / 1 MΩ (200 to 299 MΩ)
  • Test Voltage: 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0 % +25 % at 250 kΩ load
  • Test Current: > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
  • Auto Discharge Time: < 0.5 s for 1 μF
  • Max. Capacitive Load: Operational up to 1 μF

Touch Current Test

  • Display Range: 0 to 1.99 mA AC
  • Accuracy: ± (4% + 2 counts)
  • Resolution: 0.01 mA
  • Internal Resistance (via Probe): 2 kΩ
  • Measuring Method: Probe*

Substitute Leakage Current Test

  • Display Range: 0 to 19.99 mA AC
  • Accuracy: ± (2.5% + 3 counts)
  • Resolution: 0.01 mA
  • Test Voltage: 100 V AC ± 20%

Load/Leakage Test: Load Current

  • Display Range: 0 A to 13 A
  • Accuracy: ± (4% + 2 counts)
  • Resolution: 0.1 A*

Load/Leakage Test: Load Power

  • Display Range 230 V Mains: 0.0 VA to 3.2 kVA
  • Accuracy: ± (5 % + 3 counts)
  • Resolution: 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*

Load/Leakage Test: Leakage Current

  • Display Range: 0 to 19.99 mA
  • Accuracy: ± (4% + 4 counts)
  • Resolution: 0.01 mA*

PELV Test

  • Accuracy at 50 Hz: ± (2% + 3 counts)
  • Overload Protection: 300 V rms
  • Warning Threshold: 25 V rms

RCD Test: Trip Current

  • Operational Error: ±10 %
  • Nominal: 30 mA
  • Accuracy: ±5 %

RCD Test: Trip Time

  • Standard Requirement: 61557 Part 6; tolerance of rated test current 0 % to +10 %
  • Operational Error: ±10 %
  • RCD Type: AC general-purpose 30 mA
  • Display Range: 310 ms
  • Resolution: 0.1 ms
  • Accuracy: 3 ms
  • Trip Time Limit at 100 % (30 mA): 300 ms
  • Trip Time Limit at 500 % (150 mA): 40 ms

*The appliance under test is energised at mains voltage.

Environmental

  • Operating Temperature: 0 to 40 °C
  • Relative Humidity: Non condensing < 10 °C / 95% from 10 to 30 °C / 75% from 30 to 40 °C

Safety

  • Safety Rating: Complies with EN61010-1 3rd edition / CAT II, 300 V, pol 2

General

  • Size: 200 mm (L) x 275 mm (W) x 114 mm (H)
  • Weight: 3.13 kg
  • Power Supply: 230 V +10 % -15 %, 50 Hz ±2 Hz or (6500-2 only: 110V +10 % -15 %,50 Hz ±2 Hz)
  • Power Consumption (Tester): 13 W typical (idle) / 60 W max. during 25A Bond test
  • Storage Temperature: -10 to 60 °C
  • Corrosion: 70 °C @ 95 % RH for 5 days max.
  • Operating Altitude: 0 up to 2000 m
  • Sealing: IP-40 (enclosure), IP-20 (connectors)
  • EMC: Complies with EN61326-1, portable
  • EMI Immunity: 3 V/m

Supplied Accessories

The Fluke 6500-2 PAT Tester comes with:

  • Fluke 6500-2 PAT Tester
  • Instructions for Fluke 6500-2 PAT Tester
  • Test leads
  • Test probes
  • Crocodile clips
  • Mains cord
  • Storage case